HT-Instruments COMBI 420

HT-Instruments Logo

HT-Instruments COMBI 420 Multifunction VDE 0100 Tester User Manual

Model: COMBI 420

1. Introduzione

This user manual provides comprehensive instructions for the safe and effective operation of the HT-Instruments COMBI 420 Multifunction VDE 0100 Tester. The COMBI 420 is an advanced and versatile instrument designed for quick and easy verification of electrical installations. It performs tests in accordance with VDE (EN61557) parts 2, 3, 4, 6, and 7, and includes single-phase network analysis capabilities. Please read this manual thoroughly before using the device to ensure proper functionality and user safety.

2. Informazioni di sicurezza

Attenzione: Electrical testing can be hazardous. Always follow local safety regulations and procedures. Failure to do so may result in injury or damage to the equipment.

3. Produttu Finituview

The HT-Instruments COMBI 420 is a robust and user-friendly multifunction tester. It features a large, clear LCD screen with backlight and a graphical help menu for intuitive operation.

HT-Instruments COMBI 420 Multifunction Tester

Figure 3.1: HT-Instruments COMBI 420 Multifunction Tester. The device features a large LCD display, navigation buttons, and input terminals for various measurements.

3.1 Funzioni chjave

3.2 Cuntenuti di u pacchettu

The COMBI 420 package includes:

4. Setup

4.1 Installazione di batterie

The COMBI 420 requires 6 AA alkaline batteries. These are typically included with the device. To install or replace batteries:

  1. Assicuratevi chì u dispusitivu hè spenta.
  2. Truvate u compartimentu di a batteria nant'à u spinu di u dispusitivu.
  3. Aprite a tappa di u compartimentu.
  4. Inserite 6 batterie AA, rispettendu a polarità curretta (+/-) cum'è indicata in l'internu di u compartimentu.
  5. Chiudere in modu sicuru u coperchiu di u compartimentu di a batteria.

4.2 Connecting Test Leads and Accessories

Connect the appropriate test leads and accessories to the input terminals on the COMBI 420 based on the measurement you intend to perform. Always ensure connections are secure.

5. Operating Instructions

5.1 Accensione / spegnimentu

Press u POWER button to turn the device on. The device will perform a self-test and display the main menu. To turn off, press and hold the POWER button, or allow the automatic shutdown feature to activate after a period of inactivity.

5.2 Navigazione è visualizazione

Use the directional buttons and the ENTRA button to navigate through the menus and select functions. The large LCD screen displays measurement results, settings, and the graphical help menu. Press ESC / MENU to return to the previous menu or access the main menu. The AIUTI button provides on-screen assistance for current functions.

5.3 Funzioni di misurazione

The COMBI 420 offers a wide range of measurement capabilities. Always refer to the on-screen help or specific sections of this manual for detailed connection diagrams and procedures for each test.

  1. Low-Ohm Measurement (Continuity):

    Measures resistance with a test current of >200 mA DC, compliant with VDE 0413 part 4 (EN 61557-4). Used to verify the continuity of protective conductors and equipotential bonding.

  2. Test d'isolazione:

    Performs insulation resistance measurements at 50, 100, 250, 500, or 1000 V DC, compliant with VDE 0413 part 2 (EN 61557-2). Essential for checking the integrity of insulation in electrical systems.

  3. FI (RCD) Test and Analysis:

    Comprehensive testing of Residual Current Devices (RCDs) according to VDE 0413 part 6 (EN 61557-6). Includes trip time, trip current, and contact voltage misure.

  4. Loop and Network Impedance Measurement:

    Measures loop impedance and network impedance, compliant with VDE 0413 part 3 (EN 61557-3). This is crucial for determining prospective fault current and ensuring proper circuit breaker operation.

  5. Short-Circuit Current Ik Display:

    Displays the calculated prospective short-circuit current (Ik) based on impedance measurements, as per VDE 0413 part 3 (EN 61557-3).

  6. Loop Resistance without RCD Tripping:

    Allows loop resistance measurement in circuits protected by RCDs without causing the RCD to trip, using a low test current.

  7. Rotating Field Direction Measurement:

    Determines the phase sequence (rotating field direction) in three-phase systems, compliant with VDE 0413 part 7 (EN 61557-7). This can be performed even with a single test probe.

  8. Power Measurement and Harmonic Analysis:

    Measures active, reactive, and apparent power, as well as power factor. Performs harmonic analysis of voltage and current up to the 49th harmonic and calculates Total Harmonic Distortion (THD) in percentage.

  9. External Probe Measurements:

    When connected, the device can display readings from external humidity, temperature, light (lux), and sound level probes.

5.4 Archiviazione è trasferimentu di dati

The COMBI 420 has an internal memory capable of storing up to 600 measurement values. Use the SAVE button to store current measurement results. Data can be transferred to a PC using the integrated optical USB interface and the provided Topview software.

6. Mantenimentu

6.1 Pulizia

Clean the device regularly with a soft, dry cloth. Do not use abrasive cleaners or solvents. Ensure no moisture enters the device.

6.2 Sustituzione di batterie

Replace batteries when the low battery indicator appears on the display. Refer to Section 4.1 for battery installation instructions. Always use new, high-quality AA alkaline batteries.

6.3 Calibrazione

For continued accuracy and compliance, periodic calibration by an authorized service center is recommended. The device is supplied with an ISO 9000 calibration protocol, indicating its initial calibration status.

7. Risoluzione di prublemi

If you encounter issues with your COMBI 420, try the following basic troubleshooting steps:

For more complex issues, utilize the device's built-in graphical help menu or contact HT-Instruments technical support.

8. Specificazioni

FeatureSpecificazione
Numero di mudelluCOMBI 420
U fabricatoreHT-Instruments
Dimensioni di u produttu (L x W x H)24 x 17 x 8 cm (circa 9.45 x 6.69 x 3.15 pollici)
Pesu3 kg (circa 6.6 lbs)
Fonte d'energiaBattery-Powered (6 AA batteries required, included)
Cunsigliu di SicurezzaIEC-1010-1, CAT III 415 V
Norme di misurazioneVDE (EN61557) parts 2, 3, 4, 6, 7
Memoria interna600 measurement values
InterfacciaUSB otticu
Cumpunenti inclusiTopview software, USB cable, storage bag, measurement cable with earthed plug, 3 safety test leads, 2 test probes, 3 crocodile clips, batteries, user manual, ISO 9000 calibration protocol

9. Garanzia è Support

HT-Instruments products are manufactured to high quality standards. For specific warranty information, please refer to the documentation included with your purchase or visit the official HT-Instruments website. For technical support, service, or inquiries regarding calibration, please contact your local HT-Instruments distributor or customer service department.