Intermatic T174

Intermatic T174 DPST 24 Hour Time Switch Instruction Manual

Modellu: T174

Introduzione

This manual provides instructions for the installation, operation, and maintenance of the Intermatic T174 DPST 24 Hour Time Switch. This electromechanical timer is designed for controlling electrical loads over a 24-hour period.

Intermatic T174 DPST 24 Hour Time Switch with Type 1 Indoor Enclosure

Image: Intermatic T174 DPST 24 Hour Time Switch. This image shows the front view of the timer with its gray metal enclosure and the dial for setting time.

Informazioni di sicurezza

WARNING: Risk of electric shock. Installation and servicing must be performed by qualified personnel only. Disconnect power at the circuit breaker or fuse box before installing or servicing the timer.

  • Segui sempre i codici è i regulamenti elettrici lucali.
  • Ensure the power supply matches the timer's voltage rating (208-277V AC).
  • Do not exceed the maximum current and horsepower ratings of the timer.
  • This device is intended for indoor use in a Type 1 enclosure.

Cuntenutu di u pacchettu

The Intermatic T174 Time Switch package typically includes:

  • One (1) Intermatic T174 Time Switch Unit
  • Guida d'istruzzioni
  • Two (2) Trippers for setting ON/OFF times

Installazione è installazione

The Intermatic T174 is designed for fixed installation. Proper wiring is crucial for safe and correct operation.

Muntà

  1. Choose a suitable indoor location for mounting the timer, ensuring it is protected from moisture and extreme temperatures.
  2. Securely mount the timer's enclosure to a wall or suitable surface using appropriate fasteners.

Wiring (DPST Configuration)

The T174 features a Double Pole, Single Throw (DPST) contact form, meaning it controls two independent circuits or a single 2-pole circuit simultaneously.

  1. DISCONNECT ALL POWER to the circuit at the main service panel before proceeding.
  2. Open the timer's enclosure.
  3. Connect the incoming power lines (L1 and L2 for 208-277V AC) to the designated "LINE" terminals on the timer.
  4. Connect the load wires (to the device being controlled) to the designated "LOAD" terminals. Ensure correct polarity if applicable.
  5. Assicuratevi chì tutte e cunnessione di i fili sò strette è sicure.
  6. Close the timer's enclosure securely.
  7. Ripristina u putere à u circuitu.

Cunsultate un elettricista qualificatu s'è vo ùn site micca sicuru di e prucedure di cablaggio.

Istruzzioni di funziunamentu

The T174 uses a mechanical dial and trippers to set the ON/OFF schedule.

Impostazione di l'ora attuale

  1. Rotate the timer dial clockwise until the current time aligns with the "TIME SET" arrow or indicator on the timer mechanism.
  2. Ensure AM/PM is correctly observed if the dial has such markings.

Setting ON/OFF Times

The timer comes with two trippers: one "ON" tripper and one "OFF" tripper. Additional trippers can be purchased separately (Extra Trippers 11Z965).

  1. Locate the "ON" tripper (typically silver or light-colored) and the "OFF" tripper (typically black or dark-colored).
  2. Snap the "ON" tripper onto the dial at the desired time you want the connected device to turn ON.
  3. Snap the "OFF" tripper onto the dial at the desired time you want the connected device to turn OFF.
  4. You can set up to 12 ON/OFF cycles per 24-hour period using additional trippers. The minimum time setting is 1 hour.

Override manuale

The T174 typically includes a manual override switch or lever. This allows you to temporarily turn the connected device ON or OFF without affecting the programmed schedule. Refer to the specific markings on your timer for the manual override function.

Day Skipper Function

The timer features a Day Skipper function, allowing you to prevent operation on specific days of the week. Consult the detailed instruction guide included with your unit for specific setup of this feature.

Mantenimentu

The Intermatic T174 Time Switch is designed for reliable, long-term operation with minimal maintenance.

  • Periodically inspect the timer for any signs of damage or loose connections.
  • Keep the enclosure clean and free from dust and debris.
  • Do not attempt to lubricate internal components.

Risoluzione di prublemi

Prublemu Causa Possibile Soluzione
U timer ùn opera micca. Nisuna alimentazione à u timer. Check circuit breaker or fuse. Ensure wiring connections are secure.
Connected device does not turn ON/OFF at programmed times. Incorrect tripper placement or current time setting. Verify tripper positions and ensure the current time is accurately set on the dial. Check manual override switch position.
Timer motor is noisy. Normal operation for some mechanical timers. If noise is excessive or new, contact support.
Timer operates but device does not. Faulty wiring to the load or issue with the connected device. Verify load wiring. Test the connected device directly to ensure it is functional.

Specificazioni

Feature Detail
Numero di mudellu T174
Tipu Timer elettromeccanicu
Operazione 24 ore
Nùmeru di Poli 2
Forma di cuntattu DPST-NO (Double Pole, Single Throw - Normally Open)
Voltage 208-277 V AC
Ampera 40 A
Contact HP @ 120V 2 hp
Contact HP @ 240V 5 hp
Day Skipper
Tipu di recinzione Steel, Type 1 Indoor Enclosure
Finisci Smaltu Grisgiu
Minimum Time Setting 1 ora
Impostazione di u tempu massimu 23 ore
Maximum ON/OFF Cycles 12
Dimensioni (H x L x P) 7 13/16 in x 5 in x 3 in (Approximate)
Pesu di l'articulu 2.75 - 2.8 Pounds
Included Trippers 2
UPC 078275174214
U fabricatore Intermatic Incorporated

Garanzia è Supportu

The Intermatic T174 Time Switch comes with a manufacturer's warranty. For specific warranty details, please refer to the documentation included with your product or visit the official Intermatic websitu.

For technical support, troubleshooting assistance, or to inquire about replacement parts, please contact Intermatic customer service. You can often find support information and additional resources on the Negoziu Intermatic nant'à Amazon o a so sucietà ufficiale websitu.

Documenti cunnessi - T174

Preview Intermatic T105 24-Hour Dial Time Switch: Installation, Wiring, and Operation Guide
Comprehensive guide for the Intermatic T105 24-hour mechanical dial time switch. Covers model specifications, safety warnings, wiring instructions for various configurations (SPNO, SPNC, SPDT), programming procedures, and manual operation. Includes a detailed table of electrical ratings and wire gauge recommendations.
Preview Intermatic T103 24-Hour Dial Time Switch: Installation and Operation Manual
Detailed guide for the Intermatic T103 24-Hour Dial Time Switch, covering specifications, safety warnings, wiring instructions, programming, and operation. Suitable for indoor use with 120/208/240 VAC power.
Preview Intermatic T170, T1400 & T1800 Series Electromechanical Time Switches
Comprehensive details on Intermatic T170, T1400, and T1800 Series 24-Hour Electromechanical Time Switches, covering features, specifications, ratings, model variations, and wiring diagrams for commercial, industrial, and residential applications.
Preview Intermatic T104 24-Hour Dial Time Switch - Specifications and Instructions
Comprehensive guide for the Intermatic T104 24-hour dial time switch, detailing its specifications, electrical ratings, safety warnings, wiring instructions, programming procedures, and operating guidelines. Includes technical data and troubleshooting tips.
Preview Intermatic EJ351 Interruttore Temporizzatore Murale Internu: Guida di Installazione, Programmazione è Risoluzione di i Problemi
Guida cumpleta per l'installazione, a prugrammazione è a risoluzione di i prublemi di u timer interruttore murale Intermatic EJ351. Amparate cumu impostà i prugrammi, aduprà i modi automatichi è manuali, è risolve i prublemi cumuni.
Preview Intermatic Spring Wound Interval Timer Installation and Operation Guide
Detailed installation, operation, and application guide for Intermatic spring wound interval timers (FF and FD models). Includes switch ratings, wiring diagrams, and warranty information.