1. Introduzione
This manual provides essential instructions for the safe and effective operation of the Benning IT 115 True RMS Installation Tester. This multifunction device is designed for testing electrical installations in accordance with international standards such as DIN VDE 0100-600, IEC 60364-6, DIN VDE 0105-100, and EN 50110. Please read this manual thoroughly before using the instrument.
2. Informazioni di sicurezza
WARNING: Electrical shock hazard. Improper use of this instrument can result in injury or death. Always follow safety precautions.
- Always disconnect all test leads and switch off the instrument before opening the battery/fuse cover.
- Do not open the battery compartment if hazardous voltage hè presente.
- Ensure the instrument is in good working condition before use. Do not use if damaged.
- Observe all local and national safety regulations for electrical work.
- Only use the provided accessories or approved replacements.
- Ùn pruvate à misurà u voltages or currents exceeding the instrument's specified limits.
3. Produttu Finituview
The Benning IT 115 is a robust installation tester featuring a backlit graphic display and intuitive controls. It is designed for comprehensive electrical installation testing.

Figura 3.1: Fronte view of the Benning IT 115 Installation Tester, showing the display, rotary switch, and control buttons.
I cumpunenti chjave include:
- Graphic Display: Backlit screen for clear readings and connection diagrams.
- Interruttore rotativu: Selects measurement functions (e.g., R_ISO, R_LOW, Z_L-N/L, Z_L-PE, FI/RCD, SETTINGS).
- Buttuni di cuntrollu: Navigation, TEST, ON/OFF, HELP, ESC.
- Test Lead Connections: Input terminals for test leads.
- Indicatori LED: Green/red LEDs provide quick pass/fail indications.

Figura 3.2: Posteriore view of the Benning IT 115, showing the battery compartment and safety warnings.
4. Setup
4.1. Installazione è carica di a batteria
The Benning IT 115 operates on 6 rechargeable NiMH AA batteries. A charger is included for convenience.
- Ensure the instrument is switched off and all test leads are disconnected.
- Open the battery compartment cover on the rear of the device (refer to Figure 3.2).
- Insert the 6 NiMH AA batteries, observing correct polarity.
- Chiudere in modu sicuru u coperchiu di u compartimentu di a batteria.
- Connect the charger to the instrument's charging port and to a suitable power outlet to charge the batteries. The integrated battery charging function will manage the charging process.
NOTE: Do not use non-rechargeable alkaline batteries with the integrated charging function.
4.2. Cunnessione di i cavi di prova è di l'accessori
The device comes with a set of accessories for various measurements.

Figure 4.1: Included accessories: carrying case, test leads, probes, crocodile clips, and rechargeable batteries.
- Connect the test cable with the protective contact plug for standard outlet measurements.
- For other measurements, use the 3-conductor universal cable (1.5 m length) with the provided test probes or crocodile clips as required by the specific test.
- Ensure all connections are secure before performing any tests.
5. Operating Instructions
The Benning IT 115 offers a range of measurement functions accessible via the rotary switch and control buttons. The graphic display provides clear readings and a help function with connection diagrams.
5.1. Powering On / Off
Press u ON/OFF button to switch the instrument on or off.
5.2. Insulation Resistance Measurement (R_ISO)
Measures insulation resistance between 0.01 MOhm and 1000 MOhm.
- Turn the switch rotary in R_ISO.
- Select the desired nominal test voltage (50V, 100V, 250V, 500V, 1000V) using the navigation buttons.
- Connect the test leads to the circuit under test as indicated by the on-screen help diagram.
- Press u TEST buttone per inizià a misurazione.
- The result will be displayed, and the green/red LEDs will indicate pass/fail based on set limits.
5.3. Low-Ohm Resistance Measurement (R_LOW)
Measures low resistance from 0.01 Ohm to 2000 Ohms, typically for protective conductor continuity.
- Turn the switch rotary in R_LOW.
- Connect the test leads to the protective conductor.
- Press u TEST button. The instrument uses a 200 mA test current with polarity reversal and a 7 mA test current for continuity.
- Observe the displayed resistance value.
5.4. Earth Resistance Measurement (R_E)
Measures earth resistance using the 3-conductor method (requires optional earthing kit 044113).
- Turn the switch rotary in R_E.
- Connect the optional earthing kit according to the on-screen diagram.
- Press u TEST buttone.
- The earth resistance value will be displayed.
5.5. Loop and Line Impedance Measurement (Z_L-N/L, Z_L-PE)
Measures loop impedance (0.01 Ohm - 10 kOhm) for fault current path and short-circuit current determination.
- Line Impedance (Z_L-N/L): Measures impedance between Line and Neutral or Line and Line, including voltage drop and short-circuit current.
- Loop Impedance (Z_L-PE): Measures impedance between Line and Protective Earth without tripping RCD/FI, including short-circuit current.
- Turn the switch rotary in Z_L-N/L or Z_L-PE.
- Connect the test leads to the appropriate points in the circuit.
- Press u TEST buttone.
- The impedance value and calculated short-circuit current will be displayed.
5.6. RCD/FI Test
Tests Residual Current Devices (RCDs) / Fault Current Circuit Breakers (FI) of types AC, A, and F, including standard and delayed (S) types.
- Tests include automatic test sequences, touch voltage, trip time, and trip current (ramp test).
- Features an RCD/FI analysis function.
- Turn the switch rotary in FI/RCD.
- Select the RCD type (AC, A, F) and nominal current using the navigation buttons.
- Connect the test leads to the circuit protected by the RCD.
- Press u TEST button to start the test sequence.
- The results (trip time, trip current, touch voltage) s'affichera.
5.7. Rotary Field Test
Determina a sequenza di fasi in sistemi trifase.
- Turn the rotary switch to the rotary field test setting (refer to the device's specific icon).
- Connect the test leads to the three phases.
- The display will indicate the phase sequence.
5.8. voltage misurazione di frequenza
Misure AC/DC voltage è frequenza.
- Voltage Gamma: 1 V - 550 V AC/DC (True RMS measurement).
- Gamma di frequenza: 0 Hz - 500 Hz.
- The instrument continuously monitors line voltage.
- Cunnette i fili di prova à u voltage fonte.
- U voltage and frequency will be displayed automatically.
5.9. Help Function
The integrated help function provides connection diagrams and guidance for each measurement. Press the AIUTI button to access it.
6. Mantenimentu
6.1. Pulizia
Clean the instrument regularly with a soft, damp tela. Ùn aduprate micca detergenti abrasivi o solventi.
6.2. Cura di batterie
Recharge the NiMH batteries when the low battery indicator appears. If the instrument will not be used for an extended period, it is recommended to fully charge the batteries and store the device in a cool, dry place.
6.3. Sostituzione di fusible
The instrument uses a 0.315 A fuse (part number 757211). If a fuse blows, ensure the instrument is off and disconnected from all circuits before replacing it. Only use fuses of the specified type and rating.
7. Risoluzione di prublemi
- U strumentu ùn s'accende micca: Check battery charge level. Ensure batteries are correctly inserted.
- Letture imprecise: Ensure test leads are properly connected and not damaged. Verify the correct measurement function is selected.
- RCD/FI test fails: Check RCD type and nominal current settings. Ensure the RCD itself is functional.
- Display shows "OVERLOAD" or "OL": The measured value exceeds the instrument's range for the selected function. Disconnect immediately.
If problems persist, contact Benning customer support or a qualified service technician.
8. Specificazioni
| Feature | Specificazione |
|---|---|
| U fabricatore | Benning |
| Numero di mudellu | 044104 |
| Dimensioni (L x W x H) | 11.5 x 10.3 x 23 cm (4.5 x 4.1 x 9.1 inch) |
| Pesu | 1.01 kg (2.23 lbs) |
| Alimentazione elettrica | 6 AA NiMH rechargeable batteries (included) |
| Gamma di resistenza d'insulazione | 0.01 MOhm - 1000 MOhm |
| Test d'isolazione Voltages | 50V, 100V, 250V, 500V, 1000V |
| Low-Ohm Resistance Range | 0.01 Ohm - 2000 Ohms (200mA test current) |
| Loop/Line Impedance Range | 0.01 Ohm - 10 kOhm |
| RCD/FI Test Types | AC, A, F (Standard and Delayed 'S') |
| AC / DC Voltage Gamma | 1 V - 550 V (True RMS) |
| Gamma di Frequency | 0 Hz - 500 Hz |
| Cunfurmità | DIN VDE 0100-600, IEC 60364-6, DIN VDE 0105-100, EN 50110, IEC |
| Vol. Operativu Minimutage | 50 Volts |
| Volu Operativu Massimutage | 600 Volts |
9. Garanzia è Support
Benning provides a 1-year availability for spare parts for the IT 115 Installation Tester. For technical support, service, or warranty claims, please contact your local Benning distributor or visit the official Benning websitu.
Always refer to the official Benning documentation for the most up-to-date warranty terms and support information.