1. Introduzione
This manual provides detailed instructions for the installation, operation, and maintenance of the Functional Devices RIB01BDC Dry Contact Relay. Please read this manual thoroughly before installation and operation to ensure safe and proper use of the device.
The RIB01BDC is an enclosed relay featuring a 20 Amp SPDT (Single Pole Double Throw) contact, a Class 2 dry contact input, and a 120 VAC power input. It is designed for various control applications where a dry contact input is used to switch a higher voltage or current load.
2. Informazioni di sicurezza
WARNING: Risk of Electric Shock. Disconnect power before installation or servicing.
- L'installazione è a manutenzione devenu esse effettuate solu da persunale qualificatu.
- Assicuratevi chì tutti i codici elettrici lucali è naziunali sianu rispettati.
- Ùn superate micca i valori elettrichi specificati di u dispusitivu.
- Verify proper wiring connections before applying power.
- The device is designed for indoor use in a NEMA 1 housing. Protect from moisture and extreme temperatures.
3. Caratteristiche di u produttu
- 20 Amp SPDT (Single Pole Double Throw) contact for versatile switching.
- Class 2 dry contact input for control signal.
- 120 VAC power input for relay coil.
- NEMA 1 housing for general purpose indoor applications.
- Integrated LED indicator for relay activation status.
4. Specificazioni
| Parametru | Valore |
|---|---|
| Numero di mudellu | RIB01BDC |
| Tipu di cuntattu | SPDT (Singulare Polu Doppiu Lanciu) |
| Valutazione attuale | 20 Amps |
| Potenza Input Voltage | 120 Vac |
| Corrente d'ingressu di putenza | 52mA @ 120Vac |
| Input di cuntrollu | Class 2 Dry Contact |
| Alloghju | NEMA 1 Enclosed |
| Dimensioni di u produttu | 8 x 4 x 3 inch |
| Tipu di muntatura | Vite Mount |
| Materiale di cuntattu | Copper |
Valutazione di Cuntattu:
- 20 A Resistive, 277 Vac
- 20 A Ballast NO, 120/277 Vac
- 10 A Ballast NC, 120/277 Vac
- 10 A Tungsten NO, 120 Vac
- 1 HP, 120 Vac
- 2 HP, 277 Vac
- 770VA Pilot Duty, 120Vac
- 1110VA Pilot Duty, 277Vac
5. Installazione è Wiring
Refer to the product label and the diagram below for proper wiring connections. Ensure power is disconnected before beginning installation.

Figura 1: Functional Devices RIB01BDC Dry Contact Relay showing the product label with wiring instructions and contact ratings. The relay is a gray enclosed unit with a red LED indicator and a conduit connection at the bottom from which colored wires emerge.
5.1. Muntà
The RIB01BDC relay is designed for screw mounting. Secure the device to a stable surface using appropriate fasteners through the mounting tabs on the enclosure.
5.2. Istruzzioni di cablaggio
The relay features pre-wired leads for power input, low-voltage dry contact input, and relay contacts. Follow the color codes carefully.
Power Input Wires (120 Vac):
- NERU: Connect to 120 Vac Line.
- BIANCU: Cunnette vi à u neutru.
These wires supply power to the relay coil. The relay consumes approximately 52mA at 120Vac when activated.
Low-Voltage Dry-Contact Input Wires (Class 2 Wiring):
- WHITE/BLUE: One side of the dry contact input.
- WHITE/RED: Other side of the dry contact input.
These wires are for the control signal. When a dry contact closure is made across these two wires, the relay will activate.
Relay Contact Wires (SPDT):
- YELLOW (COM): Common terminal for the relay contacts.
- ORANGE (N/O): Normally Open contact. This contact closes when the relay is activated.
- BLUE (N/C): Normally Closed contact. This contact opens when the relay is activated.
Connect your load to the appropriate relay contacts (COM and N/O for normally open operation, or COM and N/C for normally closed operation) based on your application requirements and the specified contact ratings.
6. Operazione
Once properly installed and wired, the RIB01BDC relay operates as follows:
- When the 120 Vac power input is connected, the relay is ready for operation.
- The relay activates when a dry contact closure is detected across the WHITE/BLUE and WHITE/RED input wires.
- Upon activation, the integrated red LED indicator on the relay enclosure will illuminate.
- When activated, the Normally Open (N/O) contact (Orange wire) will close to the Common (COM) contact (Yellow wire).
- Simultaneously, the Normally Closed (N/C) contact (Blue wire) will open from the Common (COM) contact (Yellow wire).
- When the dry contact input opens, the relay deactivates, the LED turns off, and the contacts return to their normal state (N/O opens, N/C closes).
7. Mantenimentu
The Functional Devices RIB01BDC Dry Contact Relay is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended:
- Ispezione visuale: Periodically inspect the relay and its wiring for any signs of damage, loose connections, or overheating.
- Pulizia: Keep the enclosure clean and free of dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
- Cundizioni Ambientali: Ensure the operating environment remains within specified temperature and humidity ranges to prevent premature failure.
- Disconnection d'energia: Always disconnect power to the relay before performing any inspection or maintenance.
8. Risoluzione di prublemi
If the RIB01BDC relay is not functioning as expected, consider the following common issues and solutions:
| Prublemu | Causa Possibile | Soluzione |
|---|---|---|
| Relay does not activate (LED off) | No 120 Vac power to relay coil. Dry contact input not closed. Cablu incorrettu. | Verify 120 Vac supply to Black and White wires. Check continuity of dry contact input (White/Blue and White/Red). Review Section 5.2 for correct wiring. |
| Relay activates but load does not switch | Load not properly connected to relay contacts. Load circuit open or faulty. Load exceeds contact ratings. | Ensure load is connected to COM (Yellow) and N/O (Orange) or N/C (Blue) wires. Test the load circuit independently. Refer to Section 4 (Contact Ratings) to ensure load is within limits. |
| LED is on, but relay contacts are not switching | Internal relay failure. | If all wiring and load checks are correct, the relay may be faulty and require replacement. |
| Operazione intermittente | Connessioni di cablaggio solte. Unstable dry contact input. | Stringhje tutte e cunnessione di filu. Check the stability and reliability of the dry contact switch or sensor. |
9. Garanzia è Support
For warranty information and technical support, please contact Functional Devices, Inc. directly. Refer to their official websitu o l'imballu di u pruduttu per i dettagli di cuntattu più recenti.
Note: Specific warranty terms and conditions may vary. Please retain your proof of purchase.