Elitech VG-760

Manuale d'istruzzioni di u manometru di vacuumu digitale Elitech VG-760 HVAC Micron

1. Introduzione

This manual provides detailed instructions for the proper use, setup, operation, maintenance, and troubleshooting of the Elitech VG-760 Digital HVAC Micron Vacuum Gauge. This device is designed for accurate vacuum measurement in HVAC and refrigeration systems, ensuring efficient and reliable performance.

The Elitech VG-760 is a robust digital vacuum gauge featuring a wide measurement range, high accuracy, and multiple measurement units. It is built with an IP65 rating for enhanced protection against environmental factors.

2. Informazioni di sicurezza

  • Always wear appropriate personal protective equipment (PPE) when working with HVAC/R systems.
  • Ensure the system is depressurized before connecting or disconnecting the vacuum gauge.
  • Do not expose the gauge to extreme temperatures or corrosive substances.
  • Handle the gauge with care to prevent damage to the sensor.
  • Mantene u dispusitivu luntanu da i zitelli.

3. Produttu Finituview

The Elitech VG-760 Digital HVAC Micron Vacuum Gauge is designed for precise vacuum measurement. Its compact design and clear display make it suitable for various applications.

Elitech VG-760 Digital Vacuum Gauge

Figure 1: Elitech VG-760 Digital Vacuum Gauge, showing its compact design and digital display.

3.1 Funzioni chjave

  • Wide Measurement Range: 0-19000 Microns.
  • High Accuracy: ±10% or ±10 Micron.
  • Multiple Measurement Units: inHg, Torr, psi, mbar, mTorr, Pa, micron, Kpa.
  • Settable High/Low Pressure Alarms.
  • IP65 Rated for enhanced protection.
  • Long Battery Life: Up to 300 hours with 3 AA batteries.

3.2 Display and Button Functions

Elitech VG-760 display and button functions

Figure 2: Elitech VG-760 display elements and button controls. 1. Battery Level, 2. Auto OFF (15 min), 3. Current Vacuum Value, 4. Units. Buttons: A (Backlight on/off), B (Power on/off), C (Switch units). Pressing A+B enables auto-off.

Elitech VG-760 display showing 8 units

Figure 3: The Elitech VG-760 supports 8 different measurement units: inHg, Torr, psia, mbar, mTorr, Pa, micron, and kPa.

3.3 Filtering Components

Elitech VG-760 multiple filtering components

Figura 4: Exploded view of the Elitech VG-760's multiple filtering system, including the O-ring, Filter Net, Filter Cotton, and 1/4" SAE Fitting, designed to protect the sensor from contaminants.

4. Setup

4.1 Unpacking

Upon receiving your Elitech VG-760, carefully unpack all components. The packing list typically includes:

Elitech VG-760 packing list and contents

Figure 5: Contents of the Elitech VG-760 package, including the vacuum gauge, user manual, AA batteries, zip bag, filter cotton, filter net, and O-rings.

  • 1 x Vacuum Gauge
  • 1 x Manuale d'utilizatore
  • 3 x batterie AA
  • 1 x Zip Bag
  • 2 x Filter Cotton & Filter Net
  • 2 x O-ring

4.2 Installazione di batterie

  1. Locate the battery compartment on the back of the gauge.
  2. Aprite a tappa di u compartimentu.
  3. Inserite 3 batterie AA, assicurendu a polarità curretta.
  4. Chiudere in modu sicuru u coperchiu di u compartimentu di a batteria.

4.3 Connecting to the System

The VG-760 features a 1/4" SAE male flare fitting for connection to HVAC/R systems. Ensure all connections are tight to prevent leaks.

Video 1: Demonstrates how to connect the Elitech VG-760 to an HVAC system using a T-connector and bend adapter for vacuum measurement. It highlights the oil-proof film protection on the sensor and the process of attaching the gauge to a vacuum pump.

  1. Attach the VG-760 to the system using appropriate fittings (e.g., T-connector and bend adapter).
  2. Ensure the connection is secure and leak-free.

5. Operating Instructions

5.1 Power On/Off

Press u putenza button (center button) to turn the gauge on or off.

5.2 Controlu di retroilluminazione

Press u Retroilluminazione button (left button) to toggle the display backlight on or off for improved visibility in various lighting conditions.

5.3 Unità di misura di commutazione

Press u UNITÀ button (right button) to cycle through the available measurement units: inHg, Torr, psi, mbar, mTorr, Pa, micron, and Kpa.

5.4 Funzione Auto-Off

The gauge features an auto-off function to conserve battery life. To enable or disable this feature, press and hold both the Retroilluminazione è putenza i buttoni simultaneamente.

5.5 Interpreting Readings

The gauge displays the vacuum value in real-time. If the display shows dashes (-----), it indicates that the current pressure exceeds the measurement range of the gauge (above 19,000 microns).

6. Mantenimentu

6.1 Pulizia di sensori

If the vacuum gauge sensor becomes contaminated with oil, it may display no value or inaccurate readings. In such cases, it is necessary to clean the vacuum sensor.

Video 2: Illustrates the importance of cleaning the vacuum sensor if it becomes contaminated with oil, as contamination can prevent accurate readings. The video shows how to access and clean the sensor using a solvent.

  1. Disconnect the gauge from the system.
  2. Carefully remove the 1/4" SAE fitting to expose the sensor.
  3. Use a suitable solvent (e.g., isopropyl alcohol) and a lint-free cloth or cotton swab to gently clean the sensor surface.
  4. Allow the sensor to dry completely before reassembling.
  5. Replace the O-ring, filter net, and filter cotton as needed to ensure proper sealing and filtration.

6.2 Cura Generale

  • Store the gauge in its protective zip bag when not in use.
  • Avoid dropping or subjecting the gauge to strong impacts.
  • Asciugà l'esternu cun un soffiu, damp pannu secondu i bisogni. Ùn aduprate micca detergenti abrasivi.

7. Risoluzione di prublemi

PrublemuCausa PossibileSoluzione
U misuratore ùn s'accende miccaBatterie morte o installate incorrectamenteSustituite e batterie o verificate a polarità
Display shows dashes (-----)Pressure is above 19,000 microns (out of range)Continue evacuation until pressure drops within range
Inaccurate or no readingContaminated sensor (oil, debris)Clean the vacuum sensor as per maintenance instructions
Inaccurate or no readingSystem leakCheck all connections for leaks and repair as necessary

8. Specificazioni

Elitech VG-760 dimensions and technical specifications

Figure 6: Elitech VG-760 dimensions and key technical specifications.

ParametruValore
Dimensioni di u produttu4.92 x 1.38 x 2.76 inch
Pesu di l'articulu15.52 Ounces (0.6 lbs)
Numeru di mudellu di l'articuluVG-760
Batterie3 batterie AA (incluse)
U fabricatoreElitech
MaterialePlastica
Gamma di misura0-19000 micron
Accuratezza±10% or ±10 Micron
Temperature di funziunamentu0°F~140°F (-17.8°C~60°C)
Fitting1/4" SAE Male Flare
A vita di a batteriaFinu à 300 ore
Livellu di prutezzioneClassificazione IP65

9. Garanzia infurmazione

Elitech products are manufactured to high-quality standards. For specific warranty terms and conditions, please refer to the warranty card included with your product or contact Elitech customer support. Keep your purchase receipt as proof of purchase for warranty claims.

10. Assistenza Clienti

For technical assistance, troubleshooting, or any inquiries regarding your Elitech VG-760 Digital HVAC Micron Vacuum Gauge, please contact Elitech customer support.

  • Supportu per email: Disponibile 24/7
  • Assistenza telefonica: Available for US customers

Please visit the official Elitech websitu per l'infurmazioni di cuntattu è e risorse di supportu più aggiornate.

Documenti cunnessi - VG-760

Preview Elitech MS-100 Manometru digitale per manifold: caratteristiche, funziunamentu è specifiche
Guida cumpleta à u misuratore digitale di manifold Elitech MS-100, chì copre e so caratteristiche, u funziunamentu rapidu, e specifiche tecniche, e precauzioni è i dettagli di u produttu per i sistemi HVAC è di refrigerazione.
Preview Manuale d'usu di u manometru digitale di manifold Elitech serie MS
Manuale d'usu per u manometru digitale di manifold Elitech MS Series, chì copre a descrizzione di u produttu, e generalitàview, funzioni di i buttoni, specifiche, guida di avvio rapidu, passi operativi, applicazioni intelligenti è manutenzione.
Preview Manuale d'usu di u manometru digitale intelligente Elitech MS-100 PLUS
Manuale d'usu cumpletu per u misuratore di manifold digitale intelligente Elitech MS-100 PLUS, chì copre l'introduzione di u produttu, l'istruzzioni di sicurezza, più diview, funzioni di i buttoni, parametri tecnichi è guide d'operazione rapida per i sistemi di refrigerazione è HVAC.
Preview VGW 760 Wireless Digital Vacuum Gauge User Manual
Comprehensive user manual for the Elitech VGW 760 Wireless Digital Vacuum Gauge, covering overview, features, specifications, operation instructions, cleaning, app usage, warnings, and package contents for HVAC and refrigeration applications.
Preview Elitech MS-100 Digital Manifold Gauge Manuale d'uso
Manuale d'usu per u manometru digitale Elitech MS-100, chì detalla e so caratteristiche, u funziunamentu, e specifiche è a manutenzione.
Preview Manuale d'usu è specifiche di u manometru digitale di manifold Elitech MS-800 Series
Manuale d'usu cumpletu per u strumentu digitale di manifold Elitech MS-800 Series, chì copre l'introduzione di u produttu, e linee guida di sicurezza, a prutezzione ambientale, e specifiche dettagliate è e guide d'operazione rapida per e misurazioni di pressione è temperatura, i testi di pressione di mantenimentu è a carica di refrigerante per i sistemi HVAC è di refrigerazione.